2 Ton 14 SEER Goodman Straight Cool Package Unit GPC1424H41 Adapters

$2,063.00

Clear

$2,063.00

Clear
Compare
SKU: GPC1424H41+HKR-05 Categories: , Tags: , , ,

Description

Standard Features
• Energy-efficient compressor
• Multi-speed ECM indoor blower motor
• Quiet horizontal discharge
• Copper tube/aluminum fin condenser coil
• All-aluminum evaporator coil
• Totally enclosed, permanently lubricated condenser fan motor
• Fully charged system
• 5 kW to 20 kW electric heat kit available as a field-installed option
AHRI Certified; ETL Listed

Cabinet Features
• Heavy-gauge galvanized-steel cabinet with attractive Architectural Gray powder-paint finish
• Louvered condenser coil protection
• Aluminum foil-facing internal insulation reinforced with fiberglass scrim
• Fully insulated blower compartment with convenient access panels
• Meets cabinet air leakage requirements when tested in accordance with ASHRAE standard 193
• One footprint for all tonnages

GPC1424H41
Cooling Capacity
Cooling Capacity (BTU/h) 23,600
Sensible BTU/h 17,500
SEER / EER 14.0 / 12.0
Decibels 76
AHRI Numbers 7428120
Evaporator Motor
Type ECM
Wheel (D x W) 10 x 8
Cooling CFM 875
Fan-Only CFM 800
RLA 1.5
No. of Speeds 5
Horsepower – RPM ½ – 1050
Evaporator Coil
Face Area (ft²) 5.25
Rows Deep/ Fins per Inch 3/ 14
Indoor Orifice Size 0.055
Filter Size (“) 20 x 20 x 1
All-aluminum coil X
Drain Size (NPT) ¾”
Refrigerant Charge (oz.) 51
Condenser Fan / Coil
Horsepower – RPM 1/6 – 815
RLA/LRA 1.1 / 1.7
Fan Diameter/ # Fan Blades 22 / 2
Face Area (ft²) 9.3
Rows Deep/ Fins per Inch 1 / 27
Compressor
Quantity / Type 1 / Rotary
Stage Single
Compressor RLA/LRA 7.7/37
Electrical Data
Voltage-Phase (60 Hz) 208/230-1
Indoor Blower FLA 3.8
Outdoor Fan RLA 1.1
Total Unit Amps 12.6
Min. Circuit Ampacity¹ 15
Max. Overcurrent Protection (amps)² 20
Ship Weight (lbs) 300
Operating Weight (lbs) 305

 

Additional information

Weight 300 lbs
Dimensions 33 × 66 × 30.5 in
Heat Strip KW

, ,

HVAC Warehouse