Description

This system comes with free square to round adapters and up to 10 kw Heater W/O Breaker for Free!!

 

Standard Features
• Energy-efficient scroll compressor
• Multi-speed ECM indoor blower motor
• Quiet horizontal discharge
• All-aluminum evaporator coil
• Copper tube/aluminum fin condenser coil
• Totally enclosed, permanently lubricated condenser fan motor
• Fully charged system
• Electric heat kit available as a field-installed option
AHRI Certified; ETL Listed

Cabinet Features
• Heavy-gauge galvanized-steel cabinet with Architectural Gray powder-paint finish
• Aluminum foil-facing internal insulation reinforced with fiberglass scrim
• Fully insulated blower compartment with convenient access panels
• Meets cabinet air leakage requirements when tested in accordance with ASHRAE standard 193
• Louvered condenser coil protection
• One footprint for all tonnages

  GPH1442H41
Cooling Capacity
AHRI Cooling Capacity (BTU/h)
Sensible BTU/h
SEER / EER
Decibels
AHRI Numbers
40,500
30,000
14.0 / 12.0
78
7428307
Heating Capacity
BTU/h (47°F)
C.O.P. (47°F) BTU/h (17°F)
C.O.P. (17°F)
HSPF
37,600
3.8
21,600
2.4
8.0
Evaporator Motor
Type
Wheel (D x W) Cooling CFM Fan-Only CFM RLA
No. of Speeds
Horsepower – RPM
ECM 10 x 8
1,300
1,200
3.8
5
½ – 1,050
Evaporator Coil
Face Area (ft2)
Rows Deep/ Fins per Inch Indoor Metering Device Size Filter Size (ft
2)
Drain Size (NPT)
Refrigerant Charge (oz.)
6.2
4/ 14
0.074
(2) 20 x 20 x 1
¾” 132
Condenser Fan / Coil Horsepower – RPM RLA/LRA
Fan Diameter / # Fan Blades
Face Area (ft
2)
Outdoor Metering Device Size Rows Deep/ Fins per Inch
¼ – 1075
1.4 / 2.9
22 / 4
17
0.065
1 / 24
Compressor
Quantity / Type / Stage Compressor RLA/LRA
1 / Scroll / Single 17.9 / 112
Electrical Data Voltage/ Phase (60 Hz) Indoor Blower FLA Outdoor Fan RLA
Total Unit Amps
Min. Circuit Ampacity¹
Min. Overcurrent Protection (amps)²
208-230/ 1
3.8
1.4
23.1
28
45
Operating & Ship Weights (lbs) 375 / 385

Additional information

Weight 387 lbs
Dimensions 66 × 34 × 35 in