- You cannot add "2.5 Ton 14 SEER Goodman HEAT PUMP Condenser GSZ140301 R410a" to the cart because the product is out of stock.
STOREWIDE SALE ADD TO CART TO SEE SAVINGS
5 Ton 14 SEER Goodman A/C Straight Cool System GSX140601 & ASPT61D14 Install Kit 30′ Line Set
Install Kit Includes:
* 30′ Copper Insulated Line Set
* Drain Float Switch
* 6′ Electrical Whip
* 60 amp non fused disconnect
* Plastic Condenser Pad
* Digital Thermostat
* Heat Strip up to 10 kw
Standard Features
• Energy-efficient compressor
• Single-speed condenser fan motor
• Factory-installed filter drier
• Copper tube/aluminum fin coil
• Service valves with sweat connections
and easy-access gauge ports
• Contactor with lug connection
• Ground lug connection
• AHRI Certified; ETL Listed
Cabinet Features
• Heavy-gauge galvanized-steel cabinet with a louvered sound control top
• Attractive Architectural Gray powder-paint finish with 500-hour salt-spray approval
• Steel louver coil guard
• Top and side maintenance access
• Single-panel access to controls with space
provided for field-installed accessories
• When properly anchored, meets the 2010 Florida
Building Code unit integrity requirements for hurri-
cane-type winds (Anchor bracket kits available.)
GSX140601 | |
Capacities Max Cooling (BTU/h) |
60,000 |
SEER/EER | 14 / 11.7 |
Decibels | 75 |
Compressor | |
RLA | 25 |
LRA | 134 |
Condenser Fan Motor |
|
Hp | 1/4 |
FLA | 1.3 |
Refrigeration System Refrigerant Line Size ¹
|
|
Liquid Line Size (“O.D.) | ⅜” |
Suction Line Size (“O.D.) | 1⅛” |
Refrigerant Connection Size Liquid Valve Size (“O.D.) | ⅜” |
Suction Valve Size (“O.D.) ² ³ | ⅞” |
Valve Type | Sweat |
Charge | 120 |
Included piston: | 0.088 |
Electrical Data |
|
Voltage-Phase (60 Hz) | 208/230-1 |
Minimum Circuit Ampacity ⁴ | 32.6 |
Max. Overcurrent Protection | 50 amps |
Min/Max Volts | 197/253 |
Conduit | ½” or ¾” |
Equipment Weight Shipping Weight |
260 280 |
Product Features
• Internal factory-installed thermal expansion valves for cooling and heat pump applications
• Direct drive, multi-speed ECM blower motor
• All-aluminum evaporator coil
• Coil mounting track for quick repositioning
• Optimized for use with R-410A refrigerant
• Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in
accordance with ASHRAE standard 193
• Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in
accordance with ASHRAE standard 193
• AHRI certified; ETL listed
• Rigid SmartFrame™ cabinet
• Horizontal or vertical configuration capabilities
• 21” depth for easier attic access
• DecaBDE-free thermoplastic drain pan with secondary drain connections
• Screw-less sides and back helps to reduce condensation when installed in humid locations
• Foil-faced insulation covers the internal casing to reduce cabinet condensation
• Galvanized, leather grain-embossed finish
• Glue-less cabinet insulation retention
• Tool-less filter access
• Field Installed 3 kW – 25 kW electric heater
kits available
ASPT61D14 | |
Nominal Ratings | 60,000 |
Cooling (Btu/h) | |
Blower | |
Diameter | 11¹⁵⁄₁₆” |
Width | 10⅝” |
Coil Connections | |
Liquid | ⅜” |
Suction | ⅞” |
Coil Drain Connect (FPT) | ¾” |
Electrical Data | |
Voltage | 208/230 |
Minimum Circuit Ampacity | 8.6 / 8.6 |
Max. Overcurrent Device (Amps) | 15 / 15 |
Minimum VAC | 197 |
Maximum VAC | 253 |
Blower Motor | |
Full Load Amps (FLA) | 6.9 |
Horsepower (HP) | 1 |
Ship Weight (Lbs.) | 167 |
$4,267.00
-